Coordinated
protections of motor Starters. |
| Direct-on-line starter with Switch Fuse 400 V ,65 kA, IEC/EN 60947-4-1, AC-3, type 2 Direct-on-line Long Start start |
Table number: FM4065HDU2,2_OT | |||||||
| Motor | Switch-Fuse | Contactor | Overload Protection Device | Max. Allowed Setting Current |
||||
| Rated Output [kW] |
Rated Current [A] |
Type | Fuse Rating gG / aM [A] |
Fuse Type and Size | Type | Type | Current setting range [A] t6 setting max for starter [s] |
[A] |
| 0.37 | 1.1 | OT16E+OFAX00 | 4 | OFAM 00aM | A9 | UMC22 30* | 0,24 - 63 | 2.7 |
| 0.55 | 1.5 | OT16E+OFAX00 | 4 | OFAM 00aM | A9 | UMC22 30* | 0,24 - 63 | 2.7 |
| 0.75 | 1.9 | OT16E+OFAX00 | 4 | OFAM 00aM | A9 | UMC22 30* | 0,24 - 63 | 2.7 |
| 1.1 | 2.7 | OT16E+OFAX00 | 6 | OFAM 00aM | A9 | UMC22 30* | 0,24 - 63 | 3.7 |
| 1.5 | 3.6 | OT16E+OFAX00 | 10 | OFAM 00aM | A9 | UMC22 30* | 0,24 - 63 | 5.5 |
| 2.2 | 4.9 | OT16E+OFAX00 | 10 | OFAM 00aM | A9 | UMC22 30* | 0,24 - 63 | 5.5 |
| 3 | 6.5 | OT16E+OFAX00 | 16 | OFAM 00aM | A12 | UMC22 30* | 0,24 - 63 | 9 |
| 4 | 8.6 | OT16E+OFAX00 | 20 | OFAM 00aM | A16 | UMC22 30* | 0,24 - 63 | 12 |
| 5.5 | 11.5 | OT25E+OFAX00 | 25 | OFAM 00aM | A26 | UMC22 30* | 0,24 - 63 | 17 |
| 7.5 | 15.2 | OT45E+OFAX00 | 32 | OFAM 00aM | A30 | UMC22 30* | 0,24 - 63 | 18.9 |
| 11 | 22 | OT45E+OFAX00 | 40 | OFAM 00aM | A30 | UMC22 30* | 0,24 - 63 | 25 |
| 11 | 22 | OT45E+OFAX00 | 50 | OFAM 00aM | A30 | UMC22 30* | 0,24 - 63 | 30 |
| 15 | 29 | OT45E+OFAX00 | 50 | OFAM 00aM | A40 | UMC22 30* | 0,24 - 63 | 30 |
| 15 | 29 | OT45E+OFAX00 | 63 | OFAM 00aM | A50 | UMC22 30* | 0,24 - 63 | 35 |
| 18.5 | 35 | OT100E+OFAX00 | 80 | OFAM 00aM | A50 | UMC22 30* | 0,24 - 63 | 40 |
| 22 | 41 | OT100E+OFAX00 | 80 | OFAM 00aM | A50 | UMC22 30* | 0,24 - 63 | 48 |
| 22 | 41 | OT100E+OFAX00 | 100 | OFAM 00aM | A63 | UMC22 30* | 0,24 - 63 | 55 |
| Comments :
|
|
* : selected trip class |