Coordinated
protections of motor Starters. |
| Direct-on-line starter with Switch Fuse 400 V ,65 kA, IEC/EN 60947-4-1, AC-3, type 2 Direct-on-line Long Start start |
Table number: FG4065HDU2,2_OT | |||||||
| Motor | Switch-Fuse | Contactor | Overload Protection Device | Max. Allowed Setting Current |
||||
| Rated Output [kW] |
Rated Current [A] |
Type | Fuse Rating gG / aM [A] |
Fuse Type and Size | Type | Type | Current setting range [A] t6 setting max for starter [s] |
[A] |
| 0.37 | 1.1 | OT16E+OFAX00 | 6 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 1.5 |
| 0.55 | 1.5 | OT16E+OFAX00 | 10 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 2.7 |
| 0.75 | 1.9 | OT16E+OFAX00 | 10 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 2.7 |
| 1.1 | 2.7 | OT16E+OFAX00 | 16 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 4.5 |
| 1.5 | 3.6 | OT16E+OFAX00 | 16 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 4.5 |
| 2.2 | 4.9 | OT16E+OFAX00 | 25 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 7 |
| 3 | 6.5 | OT16E+OFAX00 | 25 | OFAA 00H | A9 | UMC22 30* | 0,24 - 63 | 7 |
| 3 | 6.5 | OT16E+OFAX00 | 32 | OFAA 00H | A12 | UMC22 30* | 0,24 - 63 | 10 |
| 4 | 8.6 | OT16E+OFAX00 | 32 | OFAA 00H | A16 | UMC22 30* | 0,24 - 63 | 10 |
| 5.5 | 11.5 | OT45E+OFAX00 | 50 | OFAA 00H | A26 | UMC22 30* | 0,24 - 63 | 14 |
| 7.5 | 15.2 | OT45E+OFAX00 | 50 | OFAA 00H | A26 | UMC22 30* | 0,24 - 63 | 16 |
| 7.5 | 15.2 | OT45E+OFAX00 | 63 | OFAA 00H | A30 | UMC22 30* | 0,24 - 63 | 21 |
| 11 | 22 | OT45E+OFAX00 | 80 | OFAA 00H | A30 | UMC22 30* | 0,24 - 63 | 26 |
| 15 | 29 | OT100E+OFAX00 | 100 | OFAA 00H | A40 | UMC22 30* | 0,24 - 63 | 32 |
| 18.5 | 35 | OT125E+OFAX00 | 125 | OFAA 00H | A50 | UMC22 30* | 0,24 - 63 | 45 |
| 22 | 41 | OT125E+OFAX00 | 125 | OFAA 00H | A50 | UMC22 30* | 0,24 - 63 | 45 |
| Comments :
|
|
* : selected trip class |