Coordinated protections of motor Starters.
Direct-on-line starter with Switch Fuse
400 V ,65 kA, IEC/EN 60947-4-1, AC-3, type 2
Direct-on-line Long Start start
Table number: FG4065HDE2.21_OT
Motor Switch-Fuse Contactor Overload Protection Device Max. Allowed
Setting Current
Rated Output
[kW]
Rated Current
[A]
Type Fuse Rating
gG / aM
[A]
Fuse Type and Size Type Type Current setting range [A]
t6 setting max for starter [s]

[A]
0.37 1.1 OT16E+OFAX00 6 OFAA 00H A9 E16DU2.7 30* 0,9 - 2,7 1.5
0.55 1.5 OT16E+OFAX00 10 OFAA 00H A9 E16DU2.7 30* 0,9 - 2,7 2.7
0.75 1.9 OT16E+OFAX00 10 OFAA 00H A9 E16DU2.7 30* 0,9 - 2,7 2.7
1.1 2.7 OT16E+OFAX00 16 OFAA 00H A9 E16DU6.3 30* 2,0 - 6,3 4.5
1.5 3.6 OT16E+OFAX00 16 OFAA 00H A9 E16DU6.3 30* 2,0 - 6,3 4.5
2.2 4.9 OT16E+OFAX00 25 OFAA 00H A9 E16DU6.3 30* 2,0 - 6,3 6.3
3 6.5 OT16E+OFAX00 25 OFAA 00H A9 E16DU18.9 30* 5,7 - 18,9 7
3 6.5 OT16E+OFAX00 32 OFAA 00H A12 E16DU18.9 30* 5,7 - 18,9 10
4 8.5 OT16E+OFAX00 32 OFAA 00H A12 E16DU18.9 30* 5,7 - 18,9 10
5.5 11.5 OT45E+OFAX 00 50 OFAA 00H A26 E45DU30 30* 9,0 - 30 14
7.5 15.5 OT45E+OFAX 00 50 OFAA 00H A26 E45DU30 30* 9,0 - 30 16
7.5 15.5 OT45E+OFAX 00 63 OFAA 00H A30 E45DU30 30* 9,0 - 30 18.9
11 22 OT45E+OFAX 00 80 OFAA 00H A30 E45DU30 30* 9,0 - 30 26
15 29 OT100E+OFAX 00 100 OFAA 00H A40 E45DU45 30* 15 - 45 32
18.5 35 OT125A+OFAX 00 125 OFAA 00H A50 E80DU 30* 27 - 80 45
22 41 OT125E+OFAX 00 125 OFAA 00H A50 E80DU 30* 27 - 80 45
22 41 OT125A+OFAX 1 160 OFAA 1H A63 E80DU 30* 27 - 80 50
Comments :
*:trip class of E_DU