Fuses
MCB
MCCB
MMS
Starting Type:
Direct-on-line Normal Start
Softstarter Normal Start Inside Delta
Star-Delta Normal Start
Softstarter Normal Start In Line
Direct-on-line Long Start
SELECT DISTINCT StartingType FROM TablesCoord_Fuses where( InterIntranet='Internet' AND Statut='validate' ) ;
Voltage (V):
400
600
500
240
415
690
480
Iq (kA) up to:
80
65
Coordination Type:
2
Motor : kW (IEC) / hp (UL)
2.2
30
22
355
11
7.5
315
250
90
132
4
1.1
37
55
0.75
110
75
45
18.5
0.37
200
3
5.5
15
0.55
295
1.5
160
Direct-on-line starter with Switch Fuse
400 V ,80 kA, IEC/EN 60947-4-1, AC-3, type 2
Direct-on-line Normal Start start
Motor
Switch-Fuse
Contactor
Overload Protection Device
Max. Allowed
Setting Current
Table
Rated
Output
[kW]
Rated
Current
[A]
Type
Fuse
Rating
gG /
aM
[A]
Fuse Type
and Size
Type
Type
Current setting
range [A]
t6 setting max
for starter [s]
[A]
2.2
4.9
OS 32D_
10
OFAM 00aM
A9
TA25DU 6,5
4,5 - 6,5
6.5
FM4080NS2,2
2.2
4.9
OS32D_
10
OFAM 00aM
A9
E16DU6.3 10*
2,0 - 6,3
6.3
FM4080NSE2.21
2.2
4.9
OS 32D_
16
OFAA 00H
A9
TA25DU 6,5
4,5 - 6,5
6.5
FG4080NS2,2
2.2
4.9
OS 32D_
16
OFAA 00H
A9
UMC22 10*
0,24 - 63
6.3
FG4080NSU2,2
2.2
4.9
OS 32D_
10
OFAM 00aM
A9
UMC22 10*
0,24 - 63
7
FM4080NSU2,2
2.2
4.9
OS32D_
16
OFAA 00H
A9
E16DU6.3 10*
2,0 - 6,3
6.3
FG4080NSE2.21
Comments :
*:trip class of E_DU
* : selected trip class