Fuses
MCB
MCCB
MMS
   Starting Type:
 Voltage (V):
 Iq (kA) up to:
 Coordination Type:
 Motor : kW (IEC) / hp (UL)

Direct-on-line starter with Switch Fuse
400 V ,80 kA, IEC/EN 60947-4-1, AC-3, type 2
Direct-on-line Normal Start start
Motor Switch-Fuse Contactor Overload Protection Device Max. Allowed
Setting Current
Table
Rated
Output
[kW]
Rated
Current
[A]
Type Fuse
Rating
gG / aM
[A]
Fuse Type
and Size
Type Type Current setting
range [A]

t6 setting max
for starter [s]

[A]
2.2 4.9 OS 32D_ 10 OFAM 00aM A9 TA25DU 6,5 4,5 - 6,5 6.5 FM4080NS2,2
2.2 4.9 OS32D_ 10 OFAM 00aM A9 E16DU6.3 10* 2,0 - 6,3 6.3 FM4080NSE2.21
2.2 4.9 OS 32D_ 16 OFAA 00H A9 TA25DU 6,5 4,5 - 6,5 6.5 FG4080NS2,2
2.2 4.9 OS 32D_ 16 OFAA 00H A9 UMC22 10* 0,24 - 63 6.3 FG4080NSU2,2
2.2 4.9 OS 32D_ 10 OFAM 00aM A9 UMC22 10* 0,24 - 63 7 FM4080NSU2,2
2.2 4.9 OS32D_ 16 OFAA 00H A9 E16DU6.3 10* 2,0 - 6,3 6.3 FG4080NSE2.21
Comments :
*:trip class of E_DU
* : selected trip class
*:trip class of E_DU